In short
- Heat pump short cycling means the compressor switches on and off far more often than it should. It wastes energy, adds wear and is often a sign of an oversized unit or poor control settings.
- The key efficiency figure in operation is the seasonal performance factor (SPF): heat delivered divided by electricity used over a year. A large European field study of 1,023 heat pumps found a two- to threefold difference between the least and most efficient systems [1][2].
- In that study, 17% of air-source and 2% of ground-source heat pumps did not meet existing efficiency standards, and about 10% of systems were oversized [1].
- A four-year field test by Fraunhofer ISE in 77 existing German homes measured average SPFs of 3.4 for air-source and 4.3 for ground-source units, and found very high switching frequencies in some systems [3].
- Measuring heat, electricity, flow temperature, starts and room temperatures shows these faults in the first winter rather than after a year of high bills.
The symptom: a heat pump that “works” but costs too much
Most underperforming heat pumps do not break down. The building is warm and nobody complains, until the electricity bill arrives. In commercial buildings, multi-family housing and public estates, this often goes unnoticed for a full season, and by then the cause is hard to reconstruct.
For installers and facilities teams this is frustrating: the owner starts to doubt the technology, when the problem is usually sizing or settings.
The metrics: COP, SPF and why they differ
| Metric | What it describes | Use |
|---|---|---|
| COP (coefficient of performance) | Heat output divided by power input at one test point in a laboratory | Comparing products |
| Weekly or monthly performance factor | Measured ratio over a period | Day-to-day monitoring |
| SPF (seasonal performance factor) | Measured ratio over a heating season or year | Judging the installed system |
Table 1: Heat pump efficiency metrics.
An SPF needs two meters: a heat meter on the heat delivered and an electricity meter covering the heat pump including any back-up heater. Without both, efficiency remains an estimate.
What field studies found
| Study | Sample | Key findings |
|---|---|---|
| ETH Zurich and University of St. Gallen, Nature Communications (2025) | 1,023 heat pumps in Central Europe, up to about two years of data | 17% of air-source and 2% of ground-source units below efficiency standards; about 10% oversized, about 1% undersized; two- to threefold spread in efficiency [1][2] |
| Fraunhofer ISE field test in existing homes (2025) | 77 heat pumps, four years | Average SPF 3.4 (air-source, range 2.6–4.9) and 4.3 (ground-source, range 3.6–5.4); some systems with very high switching frequency; no link between building age and efficiency [3] |
Table 2: Recent field studies of heat pumps in operation.
Figure 1: Range of measured SPFs in the Fraunhofer ISE field test. Own illustration based on [3].
Both studies point the same way: the same technology performs very differently depending on design, installation and settings. The authors of the Nature Communications study call for standardised post-installation performance checks and digital feedback tools [1].
Why short cycling happens
- Oversizing: a unit that is too large for the heat demand reaches its target quickly and switches off, then on again. About one in ten systems in the European study was oversized [1].
- Low system volume or closed valves: if many thermostatic valves close, the flow drops and the heat pump cannot release its heat.
- Control settings: tight hysteresis, a high heating curve or wrong buffer tank settings make the compressor start and stop more often.
- Hot water and heating mixed up: in some combination storage tanks, space heat was produced at domestic hot water temperature [3].
Figure 2: Short cycling compared with steady operation, compressor on/off over 12 hours. Schematic illustration, not measured data.
The metrics that reveal problems early
| Metric | What it shows | Typical sign of |
|---|---|---|
| Performance factor per week or month | Trend in efficiency | Deterioration after a settings change |
| Flow temperature against outdoor temperature | The actual heating curve | Curve set too high |
| Starts per day and run time per start | Cycling behaviour | Oversizing, low flow, tight controls |
| Back-up heater electricity | Share of direct electric heating | Wrong balance point or hot water settings |
| Operation in mild weather | Heating limit | Heating limit set too high |
| Room temperatures | Whether rooms need the heat | Overheated zones, room to lower flow temperature |
Table 3: Metrics for heat pump performance monitoring.
Room temperatures are the part many monitoring setups lack. They show whether the flow temperature can come down without any room getting too cold. Often a single room with an undersized radiator dictates the flow temperature for the whole building.
How Nebatic helps
Nebatic brings together data from the plant, such as heat, electricity and temperatures through the interfaces available, with room temperature, humidity and CO₂ from the rooms. Performance factors over time, flow temperature against outdoor temperature and room conditions then appear in one view. See monitoring heat pumps in operation and technical monitoring for buildings.
Which values are available depends on the plant and its meters. Nebatic does not change heat pump settings; the installer adjusts the heating curve, heating limit and hot water settings.
Risks and limits
- Metering quality: an SPF is only as good as its meters. Heat meters must be installed correctly and back-up heaters included.
- Comparability: SPFs depend on weather, hot water share and system boundary. The field data comes mostly from homes [1][3].
- No efficiency promise: only your own measurements show what a system achieves.
- Specialist work: control changes belong with a qualified heating engineer.
For the effect of night-time setback on heating, see night setback in commercial buildings.
Heat pump performance: quick answers
What is heat pump short cycling?
The compressor switching on and off many times an hour instead of running steadily. It reduces efficiency and increases wear, and often points to oversizing, low flow or control settings.
What is a good SPF for a heat pump?
In the Fraunhofer ISE field test, air-source units averaged 3.4 and ground-source units 4.3 [3]. Values well below that are a reason to check the settings.
What is the difference between COP and SPF?
COP is a laboratory value at one test point. SPF is measured in the real building over a heating season or a year.
How common are underperforming heat pumps?
In a study of 1,023 heat pumps, 17% of air-source and 2% of ground-source units did not meet existing efficiency standards [1].
How do I monitor a heat pump?
Meter heat and electricity, log flow and outdoor temperatures, count starts and run times, and add room temperatures to see whether the flow temperature can come down.
Sources
- Brudermueller, T., Potthoff, U., Fleisch, E., Wortmann, F., Staake, T. (2025): Estimation of energy efficiency of heat pumps in residential buildings using real operation data. Nature Communications 16 (abstract via RePEc). https://ideas.repec.org/a/nat/natcom/v16y2025i1d10.1038_s41467-025-58014-y.html
- Cooling Post (2025): Study finds heat pump efficiencies falling short. https://www.coolingpost.com/world-news/study-finds-heat-pump-efficiencies-falling-short/
- Fraunhofer ISE (2025): Heat pumps heat efficiently in existing buildings – research project completed (German). https://www.ise.fraunhofer.de/de/presse-und-medien/presseinformationen/2025/waermepumpen-heizen-auch-im-altbau-klimafreundlich-forschungsprojekt-des-fraunhofer-ise-abgeschlossen.html